To upgrade to the i-Vu Pro v6.0 application
Figure 1
The logic shown in Figure 2 uses a new Carrier Schedule microblock and DOES NOT use either of the
microblocks shown in Figure 1. The bottom output from the new Carrier Schedule microblock indicates if
the device is in override. If you wish to use the new Tenant Billing plug-in, you must add a binary trend
with a reference name of
override
(case sensitive) to this output, as shown in Figure 2.
Figure 2
Update your routers and controllers for the i-Vu Pro v6.0 application
IMPORTANT!
Update your routers and controllers only
once
. Use either the i-Vu
or
Field Assistant application.
Router and controller configurations are maintained when they are updated using the procedure below.
Step 1: Update the files for routers
1 Select the router that you wish to update in the navigation tree.
2 Right-click and select
Driver Properties
in the drop-down list. A dialog window appears.
3 If the database contains 2 or more routers, you must check
Change for all control programs of this type
in
the
Control Program
section.
4 Click
Update
. A message appears
Changes the driver and bacview to use the current library version.
Continue?
NOTE
If more than one router exists, the additional routers are listed below the
Update
button.
5 Click
OK.
6 Click
Close.
Step 2: Update the files for controllers
1 Double-click the controller in the navigation tree or right-click and select
Configure
.
2 If you have multiple controllers of the same type, enable
Change for all control programs of this type?
.
3 Click
Update
under
Controller
. A message appears
Changes the control program, view, driver and screen
files to use the current library version. Continue?
4 Click
OK.
When the message
Updated to the library version xx.
appears, click
Close.
5 Repeat steps 1 - 4 for any additional types of controllers.
6 Click
Close
again.
i-Vu® Application Carrier Proprietary and Confidential CARRIER CORPORATION ©2014